Supply Alert: Memory/storage supply constrained. Visit resource page or connect with Account Team for pricing and availability.
Tripp Lite EZ-Series 6000VA 5400W 230V Online 4U Rack Tower UPS System (4) C19 Outlets (SU6000RT4UHVG)
-
Temporarily Out-of-Stock
- Call for next available delivery
Ordering Information
Was
$5,400.00
$1,178.96 (21%)
Now
$4,221.04
Add to Cart
Messages
Loading
-
:
Quick View
Getting Details
Tripp Lite SU6000RT4UHVG 6000VA / 6kVA / 5400 watt on-line, double-conversion UPS system offers complete power protection for critical server, network and telecommunications equipment in a single 4U rack/tower compatible housing. Full-time active power conditioning provides clean, continuous dual-conversion AC output free of voltage fluctuations, power interruptions and line noise. Fault-tolerant auto-bypass prevents unexpected service interruptions during UPS overload or internal fault conditions. Detachable back panel PDU with manual bypass switch supports hot-swappable whole UPS replacement with no interruption to connected equipment. Single all-in-one rack / tower housing installs in only 4 rack spaces (4U) with a maximum installed depth of only 20.7 in. / 52.6cm. Maintains full-time sine wave output within 2% of selectable 200/208/220/230/240V nominal during brownouts as low 100V and overvoltages as high as 300V. Expandable runtime is supported with optional BP192V12-3U external battery packs. Battery independent restart ensures automatic UPS power-up without user interaction after lengthy power outages, even when batteries are expired and require replacement. Double-conversion operation converts raw input from AC to DC, then re-synthesizes output power back to perfect sine wave AC with enhanced protection from harmonic distortion, fast electrical impulses and other hard-to-solve power problems not addressed by other UPS types. Highly efficient operation in optional economy mode significantly reduces BTU heat output and operating energy costs. Network-grade AC surge and noise suppression. Supports detailed monitoring of equipment load levels, self-test data and utility power conditions via built-in RS-232 and USB interfaces. Optional network management card options available. HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X. PowerAlert monitoring software offers detailed site power and UPS updates with support for safe auto-shutdown of connected systems as UPS batteries become depleted. Supports Emergency Power Off (EPO) via built-in interface. Front panel LEDs and LCD readout with scroll controls support front-panel visual monitoring of all major UPS for a variety of control options to support advanced UPS settings and configurations. LED / LCD display panel rotates for viewing in rackmount or tower configurations. Hardwire input and 4 C19 outlets. Support for optional North American and International cordsets. External battery packs are field replaceable and hot swappable.
-
108.00 lbs
-
LEDS ALARMS & SWITCHES
LED Indicators: (6) LEDs indicate line power, online mode, economy/bypass mode, on-battery, charger and AC output status; LCD screen offers additional information and control options
Alarms: Unique audible alarms for all major UPS, environmental and power conditions (see manual)
Alarm cancel operation: Alarm cancel switch
Switches: main power off/on switch, plus (2) switches to set and execute scrollable LCD functions. A manual bypass switch featured on the detachable PDU allows for complete removal of the UPS during routine maintenance without disrupting power to connected loads.
SURGE / NOISE SUPPRESSION
UPS AC suppression response time: Instantaneous
EMI/RFI AC noise suppression: Yes
PHYSICAL
Installation form factors supported with included accessories: 4-post 19" rackmount (mounting kit included)
Installation form factors supported with OPTIONAL accessories: 2-post rackmount (2POSTRMKITWM); Tower (2-9USTAND)
Primary form factor: Rackmount
Secondary form factor: Tower
UPS housing material: Steel
Cooling method: Fans
COMMUNICATIONS
Communications interface: USB (HID enabled), DB-9 Serial, EPO (emergency power off), Slot for OPTIONAL SNMP/Web interface card
Network monitoring port description: Additional contact closure support with OPTIONAL RELAYIOCARD and RELAYIOMINI interface cards. RELAYIOMINI installation requires removal of panel containing USB ports
PowerAlert software: Included
Communications cable: USB, DB9 serial and EPO cables included
WatchDog compatibility: Yes
LINE/BATTERY TRANSFER
Transfer time: No transfer time (0 ms.) in online, double-conversion mode
Low voltage transfer to battery power (setpoint): 156V (full load) / 100V (50% load or less, derates linearly)
High voltage transfer to battery power (setpoint): 280V (full load) / 300V (90% load or less)
SPECIAL FEATURES
Cold Start (startup in battery mode during a power failure): Cold-start operation supported
High availability UPS features: Automatic inverter bypass, Manual bypass switch, Detachable hot-swap PDU, Hot swappable UPS power module, Hot swappable batteries
Green & high efficiency features: High efficiency economy mode operation, Schedulable daily hours of economy mode operation
CERTIFICATIONS
UPS Certifications: Tested to UL1778 (USA); Tested to CSA (Canada); Meets FCC Part 15 Category A (EMI); ROHS (Restriction of Hazardous Substances)
UPS Certification details: IEC 61000-4-5 1995 B Surge Immunity -
# Ports: 4Communication Interface: Serial (RS-232)Communication Interface: USBConnector: HardwireConnector: Power IEC 320 EN 60320 C19 (F)
-
UPS, software, rail kit, USB cable, DB9 serial cable, EPO cable, documentation
-
Attributes: Automatic voltage regulation (AVR)Attributes: Double conversion onlineColor: BlackForm Factor: 4U RackmountForm Factor: Rack-mountableForm Factor: TowerManufacturer Product Line: Tripp LiteModel: UPS Smart Online 6000VA 5400W Rackmount 6kVA 200-240V USB DB9 Manual Bypass Hot Swap C19 4URMWeight Taxonomy: 108.03lbs
-
6.9"h x 17.5"w x 20.7"d
-
Built-in UPS output receptacles: (4) C19 outlets
Output receptacle details: Output receptacle and input connections are mounted on a detachable PDU backplate with bypass switch to enable hot-swappable power module replacement
Output circuit breaker: Two 20A breakers protect (2) C19 outlets each
UPS input connection type: Hardwire -
Battery Run Time (max): 2minPower Capacity (VA): 6000VAPower Provided: 5.4kWPower Provided: 5400WSurge Suppression: StandardVoltage Provided: 192VVoltage Provided: 230V
-
OUTPUT
Output Capacity: 6000VA/5400W
Output power factor: 0.9
Output Capacity Details: Output capacity de-rates to 4992 watts when used at 208V with optional L6-30P line cord
Crest Factor: 3:1
Nominal Output Voltages Supported: 200V, 208V, 220V, 230V, 240V
Frequency compatibility: 50/60Hz (auto-selectable)
Output voltage regulation (line mode): +/- 2%
Output voltage regulation (Economy line mode): +/- 10%
Output voltage regulation (Battery mode): +/- 2%
Output AC waveform (AC mode): Pure Sine wave
Output AC waveform (battery mode): Pure Sine wave
INPUT
Rated input current (at maximum load): 31.9A (200V), 30.6A (208V), 29A (220V), 27.7A (230V), 26.6A (240V)
Nominal Input Voltages Supported: 200VAC, 208VAC, 220VAC, 230VAC, 240VAC
Nominal input voltage description: Factory configured to 208V
Recommended Electrical Service: 30A
BATTERY
Full load runtime: 2 minutes (5400 watts)
Half load runtime: 8.5 minutes (2700 watts)
Expandable battery runtime: Runtime is expandable with OPTIONAL external battery packs
External battery pack compatibility: BP192V12-3U, BP192V557C-1PH, BP192V787C-1PH, BP192V1037C-1PH, BP192V1407C-1PH
DC system voltage: 192VDC
Battery recharge rate (included batteries): 6 hours from 10% to 90% (internal batteries)
Replacement battery cartridge (internal UPS battery replacement): RBC5-192
Battery Access: Front panel battery access door
Battery replacement description: Hot-swappable, user replaceable internal batteries
VOLTAGE REGULATION
Voltage regulation description: Online, double-conversion power conditioning
Overvoltage correction: Corrects overvoltages as high as 300V (<90% load) and 280V (full load)
Undervoltage correction: Corrects undervoltages as low as 100 (<50% load) and 155V (full load), derates linearly -
Remote Management Protocol: SNMP
-
This product is subject to our return policy. Please see our complete return policy for details.
-
178 lbs
-
Compliant Standards: CSACompliant Standards: FCC Part 15 ACompliant Standards: IEC 61000-4-5Compliant Standards: RoHSCompliant Standards: UL 1778
-
39121011
-
Warranty Period: 2 years
| Description | Availability | Unit Price | ||
|---|---|---|---|---|
| View All Warranties | ||||
Batch Add Products by Item #
16