IMPORTANT: Our website will be down for planned maintenance from 5:30AM to 11:00AM EST on SUNDAY 5.17.26
-
Temporarily Out-of-Stock
- Call for next available delivery
Ordering Information
$31,816.41
Add to Cart
Messages
Loading
-
:
Quick View
Getting Details
This is a Powerware PW9355 30kVA/27kW UPS with internal battery and true Double-conversion Online topology.
-
1160.00 lbs
-
General
Diagnostics: full system self-test at startup
UPS bypass: automatic on overload or UPS failure
Parallel for Redundancy and Capacity: yes, using Powerware Hot Sync technology
Overload: (normal operation) 150% for 5 seconds / 125% for 1 minute (online), 110% for 10 minutes
Communications
LCD Display: graphical LCD with blue backlight
LEDs: (4) LEDs for notice and alarm
Audible alarms: yes
Communication ports: (1) RS-232, (1) relay contact, (1) REPO, (2) environmental input
Communication slots (2): X-Slot communication bays
Power management software: bundled software suite CD
-
Connector: Hardwire
-
UPS, documentation
-
Attributes: Double conversion onlineColor: BlackEnclosure Type: InternalForm Factor: ExternalManufacturer Product Line: EatonModel: 9355Weight Taxonomy: 1159.62lbs
-
66"h x 20"w x 34.1"d
-
Battery Run Time (max): 11minPower Capacity (VA): 30000VAPower Provided: 27kWSurge Suppression: StandardVoltage Provided: AC 220V
-
Power
Rating: 30kVA/27kW, 0.9 power factor
Topology: true double-conversion online UPS
Electrical Input
Nominal input voltage: 208/120V, 220/127V +15, -20%; 480V/277V, 600V (480+600 with transformer)
Operating frequency: 50/60Hz (45 to 65Hz)
Input power factor: 0.99 typical
Input current distortion: <5% THD
Electrical Output
Nominal output voltage: 208/120, 220/120VAC; 480/227VAC with output transformer
Output voltage regulation: ±1% Static; ±4% dynamic with 100% step load recovery within 1 ms response time
Efficiency: 91 typical
Battery
Battery type: 9Ah, sealed, lead-acid, maintenance-free
Battery replacement: field-replaceable
Charger default is 3.4A per battery string. Charger current is configurable from 0.5A to 25A per string with an overall maximum of 34A (limited by input current)
Start-On-Battery: allows start of UPS without utility input
Battery runtime, full load: 11 minutes (27kW) -
This product is subject to our return policy. Please see our complete return policy for details.
-
1190 lbs
-
Compliant Standards: CULCompliant Standards: EN 50091-2Compliant Standards: IEC 60950Compliant Standards: IEC 62040-1-1Compliant Standards: ISO 14001Compliant Standards: ISO 9001Compliant Standards: NOMCompliant Standards: ULCompliant Standards: UL 1778
-
39121011
-
Warranty Period: 90 days
| Description | Availability | Unit Price | ||
|---|---|---|---|---|
| View All Warranties | ||||
Batch Add Products by Item #
12