This website stores cookies on your computer. These cookies are used to collect information about how you interact with our website and allow us to remember you. We use this information in order to improve and customize your browsing experience and for analytics and metrics about our visitors both on this website and other media. To find out more about the cookies we use,
see our Privacy Policy.

2025 IT Superhero Awards—Nominate your IT Superheroes by July 7, 2025!
-
Temporarily Out-of-Stock
- Call for next available delivery
Ordering Information
$117,794.57
Add to Cart
Messages
Loading
-
:
Quick View
Getting Details
The APC Symmetra PX is a world class, redundant, scalable, power protection system designed to cost effectively provide high levels of availability. Seamlessly integrating into today's state-of-the-art data center designs, the Symmetra PX is a true modular system. Made up of dedicated and redundant modules -- power, intelligence, battery, bypass and all engineered into a design that is easily and efficiently serviceable -- this architecture can scale power and runtime as demand grows or as higher levels of availability are required. The Symmetra PX serves as the core power train that drives APC InfraStruXure systems for small and medium data centers but can also power individual "zones" of larger data centers. Highly manageable, the Symmetra PX features self-diagnostic capabilities and standardized modules which mitigate the risk of human error resulting in increased overall data center reliability.
This APC Symmetra PX Extended runtime model provides 100kW/100kVA of output power. Input voltages are supplied at 400V 3-phase or 480V 3-phase. Output is 400V 3-phase or 480V 3-phase. Included accessories are a user manual and a Web/SNMP network management card. Included services are Assembly Service and Start-up Service.
This APC Symmetra PX Extended runtime model provides 100kW/100kVA of output power. Input voltages are supplied at 400V 3-phase or 480V 3-phase. Output is 400V 3-phase or 480V 3-phase. Included accessories are a user manual and a Web/SNMP network management card. Included services are Assembly Service and Start-up Service.
-
5792.00 lbs
-
Included components:
UPS
(1) APC Symmetra PX 250kW Static Switch Module, 400/480V
(4) APC Symmetra PX 25kW Power Module, 400/480V
(1) APC Symmetra PX 250/500kW Battery Enclosure for up to (8) Battery Modules
Services
(1) Scheduled Assembly Service 7x24 for (1) Symmetra 250kW UPS, up to (2) XR Frames and PDU -
# Ports: 2Communication Interface: EthernetConnector: Hardwire 4-wire (3PH + G)Connector: Hardwire 5-wire (3PH + N + G)Connector: Power Hard Wire 4-wire (3PH + G)Connector: Power Hard Wire 5-wire (3PH + N + G)
-
UPS, assembly service, start-up service, Web/SNMP management card, documentation
-
Attributes: Double conversion onlineColor: BlackEnclosure Type: Plug-in moduleForm Factor: ExternalWarranty Period: 1-year warrantyWeight Taxonomy: 5804.71lbs
-
78.4"hx 92.5"w x 42.1"d
-
Output Connections: Hard Wire 4-wire (3PH + G), Hard Wire 5-wire (3PH + N + G)
Input Connections: Hard Wire 4-wire (3PH + G), Hard Wire 5-wire (3PH + N + G) -
Battery Run Time (max): 7.1minBattery Run Time (max): 7.8minPower Capacity (VA): 100000VAPower Provided: 100kWSurge Suppression: StandardVoltage Provided: 288VVoltage Provided: 400VVoltage Provided: 480V
-
Bypass Voltage Tolerance +/-10% settable from +/-4/6/8 and 10%
Output
Output Power Capacity: 100kW/100kVA
Maximum Configurable Power: 500kW/500kVA
Nominal Output Voltage: 400V 3-Ph, 480V 3-Ph
Efficiency at Half Load: 96%
Efficiency at Full Load: 96%
Output Voltage Distortion: Less than 5%
Output Frequency (sync to mains): 50Hz, 60Hz
Crest Factor: Unlimited
Waveform Type: Sine wave
Output Voltage Tolerance: +/-1% static and +/- 5% at 100% load step
Output Voltage THD: < 2% for 0 to 100% linear load and < 6% for full n
Overload Operation: 10 minutes @ 125% and 60 seconds @ 150%
Bypass: Built-in Maintenance Bypass, Built-in Static Bypass
Input
Nominal Input Voltage: 400V 3-Ph, 480V 3-Ph
Input Frequency: 40 - 70Hz (auto sensing)
Input voltage range for main operations: 340 - 460 (400V), 408 - 552 (480V)
Input Total Harmonic Distortion: Less than 5% for full load
Type of Input Protection Required: 3-pole breaker
Batteries & Runtime
Battery Type: VRLA
Included Battery Modules: (42)
Available Battery Slots: (6)
Typical recharge time: 3.5 hours
RBC Quantity: (6)
Nominal Battery Voltage: +/-288V
Efficiency in Battery Operation: 96%
Typical Backup Time at Half Load: 19.6 minutes (50,000 Watts)
Typical Backup Time at Full Load: 7.1 minutes (100,000 Watts) -
Remote Management Protocol: HTTPRemote Management Protocol: SNMP
-